Washed condenser. Blew out drain line Tested condensate pump Inspected evap coil Tested capacitor Tested charge and required sh was 23 and we had 20 which is acceptable for the unit through factory specs. Head pressure was 175psi. suction was 55 psi. 52* f outside temp