Kitchen Suppression and Portable Extinguishers Inspection Deficiency for AMEREX KP4.75 4.75G KITCHEN: No audible alarm Drops on fryers at not lined up properly and need lowered ( swivel to both drops would be lowered within specs ) 9 Holes in plenum need welded or plugged Duct needs welded and metal left of duct Electrician needed Alarm bell ( micro switches are in control box) 2 swivels Welder needed for duct Plugs for 9 holes or weld