13210 Dunnings Highway
Claysburg, PA 16625
814-239-3473

Job Locations
for duncansville, pa


Map of Duncansville PA
Jason  M.

Jason M.


Job Checkin

Annual Sprinkler Inspection Deficiency: System is past due for 5 year internal inspection and gauge replacement 5 year FDC hydro test is past due Alarms are not working since 2022 Control valves need locked open due to Alarm tampers are not working FDC has no sign above it 5 year internal inspection FDC hydro test Alarm company is needed to fix all alarms Control valves need locked open 1 water gauge Storz connection for FDC 30' lift needed for 5 year internal inspection FDC sign