Keeprite AC repair. Upon arrival condensing unit was trying to run. Condenser fan motor was spinning slowly and compressor would not start. Dual capacitor inside unit had failed. Replaced and tested operation of unit. Found refrigerant levels to be on the low end. Indoor coil was operating around freezing temperatures and system had reduced cooling capacity with 8f temp drop across coil. Added seal kit to attempt to fix the leak and charged system with 1.25 lb of 410-a refrigerant. System is operating much better now with 16f temp drop