Work Performed: No cooling call on an estimated 2017 Daikin air conditioner. Used monitoring tools to assess system. Found disconnect box melted with seized/pushed-in button causing an unsafe condition—high-voltage could not be safely turned off due to possible welded contacts. Replaced disconnect box to restore safe control of power. Found capacitor reading 42.8 µF (should be 45 µF). Replaced capacitor. Fired up unit. Client reports no professional maintenance through Evan’s but has rinsed coil with a hose themselves. Results: Inspected outdoor coil – appears in fair condition Checked amp draw – compressor drawing 16 amps and liquid line pressure rising to ~500 psi Inspected indoor evaporator coil – no visible blockages Verified secondary heat exchanger and blower speed – blower set to correct airflow for 3-ton system Cleaned condenser coil thoroughly for best operation After cleaning, pressures more stable but high-side pressure still fluctuating and compressor remains over-amping