Valour fireplace maintenance. Performed cleaning and testing on fireplace . Receiver needed the batteries changed , but no other issues found . Fireplace is in good condition and operating well . Goodman furnace maintenance. Furnace is operating very well , adjusted gas pressure back to factory recommended 1.9 inw for low fire and 3.5 inw for high fire . Humidifier is not operating at the time of service , humidistat is operating , I can faintly hear the solenoid opening and closing but no water flow . Discussed problem with customer and decided to deal with the issues at a later date . No other issues with furnace .