4065 Stanley Ave
Niagara Falls, ON L2E 4Z1
905-354-4424

Job Locations
for niagara-on-the-lake, on


Map of Niagara-on-the-Lake ON
Wesley P.

Wesley P.


Job Checkin

Work Performed: Completed full annual maintenance on furnace under existing manufacturer's warranty (Year 9 of 10). Maintenance included: Cleaned flame sensor Checked heat rise Combustion analysis Gas pressure check Cleaned combustion chamber Inspected and cleaned drain lines Visual inspection of all electrical components and wiring Tested blower motor and inducer motor amperage Verified thermostat operation Checked venting and combustion air intake for proper clearances Findings & Recommendations: The furnace is currently operating within manufacturer specifications with no safety concerns found at this time. However, signs of water damage and calcium buildup were found on the seams of the inducer motor housing, along with minor rust. These are signs of long-term condensation buildup that could lead to motor failure. The inducer motor is still covered under warranty — a part that typically costs in the hundreds of dollars — but labour is not. To avoid a costly repair after the warra