Work Performed: Addressed Enbridge red tag due to a gas leak on the main supply line. Enbridge replaced the gas meter and identified a leak near a fitting close to a union. Disassembled the union, tightened the fitting, and confirmed the leak was resolved. Performed a full gas leak test—no leaks present at this time. Noted serious safety concern with the upstairs gas stove, which has standing pilots and no safety shutoff if the pilot goes out. Gas was continuously leaking from the stove—advised replacement. Spoke with Dan and received approval to turn off gas supply to the stove for safety. Advised that the stove must be replaced and offered to install a new one if provided by the customer. A new gas hose will also be required. Turned on the water heater and furnace—both are operating properly. Results: House is leak-free, and all appliances are operational except for the gas stove, which has been shut off for safety. Red tag will be cleared by the office.