For this job, the furnace was giving an error code of 58. Which indicates water circuit open. I pulled the trap apart and done a thorough cleaning on the trap and I also blow through the drain line. I checked the continuity on both water sensors, I found them both working great. There was water on the sensor, and after I drive both of them off and reinstall the trapped, the cycle of the furnace ran normally. I could not find any other issue with the system I checked the level of the furnace and found the furnace level. I would like to see a little fall towards the front. My recommendation is this, If this occur again, I recommend replacing both water sensors and raising the back of the furnace to fall towards the front. As of right now, the furnace is working in normal operation