Burner was off on reset when arrived. Checked the oil flow, it was clean and strong. Turned the water heater on with the boiler running and there was no change in flow. Checked the nozzle assembly, there was a small dark spot on the tip of the nozzle, which indicates that the nozzle is not spraying correctly. Replaced the nozzle. Started and tested