Performed a heating pm on an oil furnace. Brushed and vacuumed. Replaced the oil filter, nozzle and strainer. Replaced the air filter, 16x25x1 Started and checked the safeties. Performed a combustion test. 7.9% o2, 33 ppm, 86.5% efficient System is operating properly. Performed an A/C pm. Blew out the drain line. Rinsed the condenser. Checked the electrical connections, checked the pressures and temps. System is operating properly. The capacitor is rated for 45/5 +/- 5% mfd, the actual was 44/1.4 mfd. The fan side is below the limits. Also the fan motor is drawing the max rated amps of 1.2 amps. The fan motor is very loud. Recommend replacing the condenser fan motor and capacitor. - the customer is turning off the system and wants to replace everything in the spring. The water heater is from 2015, recommend replacing. Customer has scheduled an appointment to replace the 40 gallon Electric hot water heater w/ a Taco Leak Breaker and pan.