Semi-Annual Kitchen Inspection Inoperable Deficiency: System is overflowed Double tank cartridge is due for replacement Duct nozzle is too small over microwave ( needs a 2W ) Plenum nozzle under chain broiler is more than 6" from end of hood System needs manifolded for proper flow coverage ( 2 Cylinders have maxed out for flows ) Duct nozzle for chain broiler is obsolete 8 metals caps are broken or will not stay on Chain broiler, convection oven fryers do not shutdown when tripped Manifold system Remove 245 nozzle beside convection oven and plug to reduce flows( no appliance) Double tank cartridge 1W nozzle 2W nozzle Electrician needed for fryers, chain broiler and convection oven to shutdown 1 stick 3/8 pipe 2 3/8 unions 4 nipples 3/8 plug 8 metal caps