Arrived at location on 7/26/22 - Removed and replaced bad compressor, charged unit with 250 psi nitrogen and let stand for 30 minutes with no drop in pressures. Vacuumed system below 500 microns and charged unit to factory specifications. Waited for unit to cycle 3 times and is operating properly at this time.