Commercial Kitchen Equipment Repair Service: The client’s griddle was overheating, causing food to cook unevenly. I performed a detailed inspection and recalibrated the temperature controls to ensure consistent cooking temperatures across the entire surface.
Commercial Kitchen Equipment Repair Service: The client’s warming drawer was failing to keep food warm. After investigating, I discovered that the heating element had burned out. I replaced the element and tested the drawer to confirm it could hold the appropriate temperature for food storage.
Commercial Kitchen Maintenance Service: Conducted a comprehensive maintenance check-up on all kitchen appliances, ensuring optimal performance and longevity.
Commercial Pizza Oven Installation. A pizzeria wanted to upgrade its menu with a new commercial pizza oven. We positioned the oven, connected the gas line and electrical wiring, and fine-tuned the temperature controls. Thorough tests ensured consistent pizza baking results, and the kitchen staff received training in operation and maintenance.
Arrived on,7-10-23- Giuliano G/Ron F-Drain needs re piped and unit needs cleaned/sanitized. Will find parts locally for drain when we come back for cleaning. Both ice machines need cleaned and repiped with 2 inch gap per codes. Returned on, 7-21-23- Giuliano G-Replaced water lines inside first floor ice machine and repiped drain to code specifications. Cleaned lines and sanitized. Ran ice machine for about 45 minutes to verify proper operation. First floor ice machine is running and up to code. Recommended getting some type of floor blocks so ice machine won’t move. Will need to come back with 3/4inch cpvc for employees ice machine to be repiped to code specifications and clean out ice tray and lines with sanitizer. Also employee mentioned they have a 3rd ice machine that may need serviced as well. Will return on latter date to finish other two ice machines. Completed on, 7-26-23- Giuliano G-Came back to repipe and sanitize employee ice machine. Maintenance must of repiped drains in
Arrived on, 7-10-23- Giuliano G/Ron F-Drain needs re piped and unit needs cleaned/sanitized. Will find parts locally for drain when we come back for cleaning. Both ice machines need cleaned and repiped with 2 inch gap per codes.Returned on, 7-21-23- Giuliano G-Replaced water lines inside first floor ice machine and repiped drain to code specifications. Cleaned lines and sanitized. Ran ice machine for about 45 minutes to verify proper operation. First floor ice machine is running and up to code. Recommended getting some type of floor blocks so ice machine won’t move. Will need to come back with 3/4inch cpvc for employees ice machine to be repiped to code specifications and clean out ice tray and lines with sanitizer. Also employee mentioned they have a 3rd ice machine that may need serviced as well. Will return on latter date to finish other two ice machines. Finished on, 7-26-23- Giuliano G-Came back to repipe and sanitize employee ice machine. Maintenance must of repiped drains in b
Commercial Kitchen Equipment Repair Service. Arrived at the location on 4/28/23 to check over their commercial kitchen equipment that required repairs- Checked over the unit. Found screws on the adjustment for the knob were loose. Secured and calibrated unit. Found all ok at this time.
Arrived at location on 1/5/23 - Checked over unit. Found when powered on unit starts cycle. Upon checking found cycle switch bad sending unit into cycles one right after the other. Found due to cycling as it was unit burnt relays on control. Will need to order switch and control. Returned to location on 1/10/23 - Replaced all parts unit comes on and is working properly.
Arrived at location on 7/12/22 - Customer explained unit not cooling and at 55°F. Found unit has leak on Johnson low pressure control on condenser. Will return tomorrow to replace and verify no other leaks. Returned to location on 7/13/22 - Replaced low pressure control and filter drier. Verified no leaks and pulled vacuum under 500 microns. Charged with 8lbs of R404a refrigerant. Verified proper operation. All is good at this time.
Arrived at location on 7/5/22 - Checked over unit. Found heated ro 325 with no issues. Customer stated unit worked fine until they set it at 300. Had customer set at 300. Noticed the heat was randomly coming on. Upon checking found potentiometer and control are needed. Will order and return. Returned to location on 7/7/22 - Replaced potentiometer and control. Tested and ran at 250, 300, and 350. All ok at this time.
Arrived at location on 6/22/22 - Customer explained unit doesn’t run. Replaced thermocouple and verified proper operation. All is good at this time.
Arrived at location on 6/13/22 - Replaced casters and verified proper operation. All is good at this time.
Arrived at location on 5/19/22 - Checked over unit. Found pilot low and thermocouple burnt. Pulled pilot to clean and found it would not go back on due to corrosion on feral and threads on pilot. Will need new pilot and thermocouple ordered. Returned to location on 6/2/22 - Replaced pilot and thermocouple. Checked for leaks and found none. Tested and found all operational at this time.
Arrived at location on 6/1/22 - Checked over unit. Found spark wire exposed at connections and was sparking on the back side of the burner. Secured connection and retested. Found sparks as it should. Let heat to ready and found all ok at this time.
Arrived at location on 5/19/22 - Door jam gaskets have rips and customer wants replaced. Returned to location on 5/24/22 - Replaced gasket and verified proper seal. All is good at this time.