Commercial Kitchen Equipment Repair: The client's beer cooler was not maintaining consistent temperatures. After recalibrating the thermostats, the cooler now keeps beverages at the ideal storage temperature.


Ashley B.

Ashley B. Job Checkin

Commercial Food Processor Repair Service: Addressing a client's concerns with their commercial food processor, I discovered that the blades were no longer spinning effectively due to a malfunctioning motor. A quick replacement of the worn-out motor rejuvenated the appliance, enabling efficient operation once more.


Ashley B.

Ashley B. Job Checkin

Fountain Machine Installation. I arrived to begin the installation of soda fountain machines for the business. Beyond installation, I calibrated the syrup lines and dispensing mechanisms to perfection, ensuring customers enjoyed refreshingly consistent beverages.


Ashley B.

Ashley B. Job Checkin

Commercial Steam Kettle Installation. A commercial culinary facility required a new steam kettle for their operations. We assessed their needs, recommended an appropriate model, and carried out a seamless installation, including steam and water line connections. Thorough tests confirmed efficient cooking capabilities for their large-scale recipes.


Ashley B.

Ashley B. Job Checkin

Commercial Walk-in Freezer Installation Service near Mt Gretna Rd. A restaurant required a new walk-in freezer installation to expand its storage capacity. We carefully assembled the walk-in freezer panels, installed the refrigeration system, and ensured proper insulation. After conducting temperature tests and confirming optimal performance, we handed over a fully functional walk-in freezer to the restaurant owner. They were delighted with the increased storage space for their perishable goods.


Mark B.

Mark B. Job Checkin

Commercial Kitchen Equipment Install near S Market St. After the ice machine at a commercial business failed them, they contacted us for a resolution. We reviewed options with the client, and they decided on the best and most affordable appliance for the business. We arrived at the scheduled date and removed the old ice machine and then installed the new ice machine into the establishment. The client was relieved to have an operable ice machine in the business!


Mark B.

Mark B. Job Checkin

Commercial Kitchen Equipment Repair Service. I arrived at the location and spoke with the customer. The customer stated they had just lit the pilot light for the griddle. Tested for gas leaks from the manifold into each piece of equipment and verified no leaks. Inspected all burner valves and all are in good condition. Good ignition on all burners. The pilot for the oven was not lit. Lit pilot and have good functions. Did find all range top burners that needed cleaning and had debris inside. The customer stated hood had recently been cleaned. Suspect not all pilots relit on the completion of hood cleaning. Pilot flames are all good and good ignition to burners. Unit ok for use.


Mark B.

Mark B. Job Checkin

Arrived at location on 10/22/21 - Arrived, stated unit is dead, not turning on at all. Turned unit on, turned hood on. Checked voltage, traced back through fuses, fuse block. Not getting voltage to power supply board. Traced through up to hood and back down to terminal blocks. While moving wiring and reconnecting terminals, now have voltage to power supply board and unit now turns on. Check ops, functioning correctly. Likely just a loose connection that is now corrected. Ok for use.


Mark B.

Mark B. Job Checkin

Arrived at location on 7/2/21 Spoke with caterers when I arrived and they told me the noise was coming from inside the box. I heard the noise the last time we were here and it was definitely coming from the condenser, which is when we re-strapped the run capacitor for the compressor. Looked inside evaporator and found ice in the drain pan, the bottom of the coil, and the distributor was a block of ice. Thawed everything with hot water. Ran five gallons of hot water down the drain to make sure the drain wasn’t slow or clogged. Went over electrical to make sure there weren’t any loose connections and checked evaporator motors/blades. Returned walk-in back into service and monitored pressures/temperatures. Found box satisfying at exactly 32 degrees. I believe the box set point was too low and when the humidity was high the evaporator wasn’t properly off cycle defrosting, causing the fan blades to strike ice. Adjusted thermostat and monitored operation. System is turning on at 35


Libby D.

Libby D. Job Checkin

JADE RANGE (left) - 4/22/2021 - Michael P A - arrived on site and inspected unit and found all lilots lit. middle burner not lighting off pilot on low setting and barely lighting at higher setting. checked and verified manifold pressure 5wc was good but not properly being passed to burner. bad thermostat. will obtain replacement and return. customer requested QWP approval from will. 4/23/2021- John H - At location with follow up parts for zone 2 from left. I replaced thermostat and tested. I followed instructions given directly from manufacturer to calibrate new gas valve and found bypass unresponsive high or low. Please note zone 2 middle didn't heat outside range while on site but didn't calibrate properly as mfg instructions. I will contact mfg Monday to get further knowledge of grill status..


Service C.

Service C. Job Checkin

Found Combi Oven making a popping noise or fluttering sound when igniting. I did pull the burners and found them OK. I did calibrate the exhaust with the flue analyzer. unit now lighting without popping. I checked ops, OK ready to use.


Service C.

Service C. Job Checkin

Cleaned Reach-In Cooler condenser coil and evaporator fan shrouds, verified good airflow, checked gaskets and hinges. Both gaskets in poor condition and need replaced, also found discharge loop in poor condition. Customer would like quoted. Unit working at this time, at 34°F.


Service C.

Service C. Job Checkin

Found bottom left combi has a leak in the steam generator and the spark is weak causing delayed ignition and popping sound. I will obtain parts and return. Steve said to repair it. I will obtain parts and return. 3/6/20 Did replace the steam generator assembly and burner and module and drain hose. I set co to 9.4% at 71 rpm. I checked ops. OK ready to use.


Service C.

Service C. Job Checkin

stated Oven unit displaying F1 error, went into test mode, run blower motor, does not run, remove covers, spin motor by hand, is rough, motor now does turn on through test mode but is very loud. blower motor going out. will order and return. 5/29/19 removed covers from unit, removed old blower motor from unit. install new. reassemble covers onto unit. plug in, turn on, allow to heat, blower now running quietly. check amp draw on heaters and mag circuits. OK on heating circuits. test make product. OK for use.


Service C.

Service C. Job Checkin

Installed customer supplied temperature controller for Conveyor Oven. I did match the perimeters with the other control. checked ops. Okay, ready to use. control came from northern pizza equipment 1 800 426 0323 MPI TEMPERATURE CONTROL