Arrived on site to install warranty evaporator coil. System void of refrigerant on arrival. Cut out faulty coil, installed new coil and line dryer. Pressure tested with nitrogen and pulled vacuum to <500 microns to remove moisture from line. Charged unit with 6 lbs 15oz r410a per manufacturer. Adjusted charge per manufacturer spec. Unit is operating normally at this time