Maintenance for cooling on an American Standard upflow located in an outside closet. filter located in the FAU 16 x 20. Upon arrival, customer complaint of no air being pushed out when called for cooling checked FAU blower motor was not on but coil and outside unit were on. Turned off system coil was freezing up. Checked blower motor check 24 V on G and R confirmed 24 V. Checked transformer noticed three amp fuse was burnt. Replaced three amp fuse blower motor came on set thermostat to cooling checked outside compressor amps Freon and pressure. Customer wanted a deep clean wash down of the outside unit. Notify customer of the cost. Customer agreed thoroughly washed. The outside. Unit down. System is working per manufacturer specification home is cooling properly