Have any feedback for us? We'd love to hear it! Call us at (760) 910-7600 and let us know how we are doing.
Our Serviceman, Mr. Jones was professional, and we believe he serviced the units properly.
Daniel Galvan was amazing ! A great tech. Knowledgeable, personable and respectful. I have never had a bad experience with a Hydes tech but he was one of the BEST! Thanks!!
Liked talking with Mike. Very open and informative. I don’t know about pricing as he is our first interview for a bid.
Christopher was very nice and polite, he went right to work and even put additional rubber on the roof so we wouldn’t hear the unit. He was great.
Daniel represents Hyde well and demonstrates why Hyde’s is the best
Upon arrival found equipment flat on refrigerant Opened entire system and look for leak Found leak at condenser coil sent over estimates with different options
Answered clients questions about estimates that were provided.
Cooling service and safety check on two systems. Verified equipment is operational at this time. Replaced filters.
Installed 5 Ton American Standard Silver 14 Condenser only for living room unit. customer said use cc on file
2009/ 4 ton Upon arrival Klein for me, system is not blowing cool air with further investigation found major short at capacitor also found contactor out of range. Recommended and replaced 55/5uF capacitor, 40A contactor and added hard start kit, repaired burnt wires Also signed up client on Heights family comfort Plant monthly membership. Performed semi annual cooling service on Goodman split heat Cleared condensation line and replaced 20 x 20 filter. Located within the air handler garage up flow. Cycled equipment followed cooling sequence of operation check refrigerant/temperature split compressor amps and voltage. Condenser coil. Thermostat checked out OK. Cooling equipment is now operating efficiently and within limits.
Sighned up for maintenance plan. Service on 2 2018 & 2020 Daikin systems. Washed coils, cleaned electrical compartments, cleared drain lines, replaced filters. Verified refrigerant pressures are good. Found capacitors out of range and replaced parts on each unit to prevent breakdown. Verified sequence of operation is working properly at this time.
Performed a cooling maintenance on two 2023 American standard platinum condenser unit, As well as also perform an inspection on both heat pumps located in attic. While checking heat pumps, tested cut off switches, checked refrigeration levels by performing a split temp was getting a 25 and a 23 degree split as this time. Blew out condensation lines, upon checking out door units checked fuses as well as used CDA to check for any alerts and electrical components. Also checked 1050 thermostat, at this time all is within manufacture specifications, and both systems are cooling properly as well as both units are ready for final inspection. Finished maintenance by washing out min split filters.
Performed a cooling maintenance on a Goodman condenser unit. Checked sequence of operations by checking refrigerant levels. As shown in pictures refrigeration levels are well within range. Also checked run capacitor and hard start kit, tested FLA and RLA. At this time all is within manufacture specifications and system is cooling down house properly at this time. Finished maintenance by blowing out condensation line from outdoor drain pipe. And by changing out filters threw out house.
Performed annual cooling maintenance on one 2023 Lennox condensing unit. Client had recently changed filter. Left client with filter cycle system and cooling. Check capacitors checked RLA checked LRA checked FLA. Checked refrigerant pressures. Washed condenser coil. Equipment is cooling properly at this time. Fone was interested in quote for a diverter gave client quote Verbally, sending estimate via email as well.
Performed cooling maintenance on 2005 York split system. Fau in inside closet. Cleaned condensing coil. Changed filter with fau. Cleared condensation drain. Checked Refrigerant pressures, superheat, subcool and temperature split were ok. Outdoor compressor pulling high starting amps 165 when rated for below 150 suggest compressor saver kit to reduce stress on motor. Equipment is operational at this time, advise equipment is past life expectancy 18 years old.
Performed a cooling maintenance on a 3.5 ton condenser unit. Checked sequence of operations by performing a split temp to check refrigerant levels was getting a 19 degree split at this time. Checked all electrical components winch as run capacitor and compressor amps. Run capacitor rated at 50 was getting 47 would recommend changing out capacitor before next summer as well as install a hard start kit to help with compressor amps. At this time system is cooling down house properly. Blew out condensation line from outdoor drain pipe located next to unit as well as washed out outdoor unit. Tennent Also already has a full box full of 18/24 does not need any at this time has already over 20 filters at this time.
Cooling service and safety check on two 2018 system. Replaced filters, washed coils, cleared drain lines from outside. Verified equipment is working properly at this time.
For this job, I worked on a ceiling fan that the remote control was not working to turn on the fan so we went ahead and put a customer supplied ceiling fan. Also, we added one Casada switch that we provided and one switch that the customer supplied and those switches one Casada switch controls the bathroom lights and the other switch controls as you walk into the bedroom the lights over the bed.
Performed annual cooling maintenance on 4 American standard split systems. Changed filter and washed washable filters, cleared condensation lines. Cycled systems in cooling, checked capacitors, LRA, rla and Fla. checked refrigerant pressures. Washed condenser coils. Found great room condenser had capacitor that was completely dead, advised client of findings and replaced. All systems are now cooling properly at this time.