Have any feedback for us? We'd love to hear it! Call us at (760) 910-7600 and let us know how we are doing.
Upon arrival outdoor unit, not turning on, with further investigation, found a blown disconnect . Informed client will need to replace before continuing diagnostic. Client agreed to have disconnect replace after doing so was getting power to outdoor unit could hear compressor trying to turn on but struggling added a hard start kit and got system up and running system is now cooling down the house properly refrigeration levels as well as power levels are within range