Heating service on two American standard ultra low Knox furnaces located in separate outside closets. Changed out 20 x 25 filters located in filter rack, verified proper operation of water, safety switches, condensation lines were cleared at Jones valves, upon a maintenance member stated system serial number 5PLG was making loud screeching noise to reduce noise, lowered system to 2.5 inches water column and tested system. Verified proper sequence of operation on both systems, cleared all electrical components and burner compartment of dust and debris, verified proper sequence of operation, zero carbon monoxide detected systems are within manufacturers, specifications, and heating and operating properly at this time of service. Also set appointment up with member for next maintenance service for June 19th between the hours of 2 PM – 5 PM