Installed new high-efficiency variable-speed split system for commercial client. System sized at 5 tons with 14 SEER rating. Performed nitrogen pressure test at 450 PSI, evacuated to 350 microns, and charged to manufacturer specs. Verified airflow at 400 CFM per ton. Advised client on programming economizer settings for spring temperature differentials.