Upon arrival unit was on. Customer stated the breaker was tripping intermittently causing the condenser to stop running. Upon inspection found multiple high and low voltage wires chewed up and touching metal. Also found the contactor was corroded and starting to pit. Repaired all chewed wires and replaced the contactor. Started unit and checked refrigerant. Unit is operating properly.