Upon arrival unit was turned off with breakers off. Turned unit on and the compressor and outdoor fan did not start. Checked the capacitor and found the fan side was open internally and the compressor was only reading 23 when it was rated for 50. Replaced the capacitor with a turbo200 universal capacitor and started and tested the unit. Refrigerant levels were good. Checked amp levels and found the compressor was running at 13 amps out of 14.8 which is very high. Took pictures and measurements for a replacement quote.