During the recent sprinkler system inspection performed by Liberty Fire Solutions, LLC the following deficiencies were found. 5 year internal inspection due per NFPA on sprinkler system NFPA 25 REQUIREMENTS FOR 5 YEAR TESTING: 13.4.1.2 Alarm valves and their associated strainers, filters, and restricted orifices shall be inspected every 5 years unless tests indicate a greater frequency is necessary 13.4.2.1 Check valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely and are in good condition 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years in accordance with 14.2.1.2 for the purpose of inspecting for the presence of foreign organic or inorganic material 14.3.2.2 Internal examination shall be performed at the following minimum four points: (1) system valve (2) riser (3) cross main (4) branch line NFPA 25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5