Annual Extinguisher Inspection (4) ABC Semi-Annual Kitchen Inspection Ansul 6 gal? Inoperable Deficiency: Both cylinders are due for hydro test and hose replacement Cartridge is due for replacement Regulator is due for testing Nozzles above fryer need replaced with 3N nozzles ( currently 230 with 14x23 fryers) Detection line failed Detectors above fryers are obsolete and need replaced Range combo has no detection where hood is split Plenum nozzle at small hood is more than 6” away No alarm or alarm bell on system Large duct needs a 2w nozzle added Alarm bell Micro switch Regulator test Double Tank cartridge Hydro test both cylinders 2 3N nozzles 3 Ansul detection brackets Nozzles need dropped 6” at fryers Plenum nozzle needs moved closer 2 3/8 6” nipples and coupler for fryers 1 stick of conduit 40’ cable 1 3/8 Tee 4 3/8 elbows