Mark B.

Mark B. Job Checkin

Arrived at location on 9/23/22 - spoke to manager as to what is going on with the unit. Customer stated the unit keeps running. Checked over all switch function and found that the final rinse lever wasn’t disengaging to show cpu that rack had passed through the system. Opened doors and found a spoon stuck below the actuator. Removed and verified all operation. Showed customer where to check if this issue happens again. Recommended that they look into new dish racks as theirs are starting to get folded over and warped underneath where the dogs catch it to pull through machine.


Mark B.

Mark B. Job Checkin

Arrived at location on 7/15/22 - Installed drain pan right below the drain line. Customer had a power surge protector mounted to the back of the unit so I used an electrical cord that I had and wired the drain pan up to it and plugged it into the surge protector. Unit is now evaporating the drain water as it should.


Mark B.

Mark B. Job Checkin

Arrived at location on 7/8/22 - Found evaporator fans not running, also found compressor contactor pulled in but compressor not running, found correct power into contactor but not coming out. I replaced contactor and condenser unit came on. I waited for unit to start coming down to temperature, unit was at 25 degrees when I left and working properly


Mark B.

Mark B. Job Checkin

Arrived at location on 7/5/22 - Checked out unit and found that the chemical line broke off and water was coming out the fitting. Repaired rinse aide line and checked operation. Found no more leaks at this time.


Mark B.

Mark B. Job Checkin

Arrived at location on 4/26/22 - Checked out unit and found the one side was not working so checked amps, no amps. There was power going to it. Pulled the bottom cover down and found the one wire was burnt off so turned power off and fixed the wire and checked operation, ok. Put everything back together and checked operation, ok.


Mark B.

Mark B. Job Checkin

Arrived at location on 4/1/22 - Checked over unit and found that the 20a fuse was blown for mag circuit. Unit had an active F3 error code as well. Pulled apart and swapped out fuse. Tested all components and found that the K2 anode relay was burnt on terminals and showed a lot of signs of arcing. Replaced fuse and went to test. I wanted to confirm due to the readings I got on the capacitors which indicated they were open on the .91 microfarad side of them. Unit popped fuse and showed F3 error again. We will need to acquire parts and return to replace. I know the one part is a tough one to get but at this point the unit is down and we need it. Returned to location on 4/4/22 - Installed new parts that were ordered for unit. Swapped out and let unit heat up to temp. After warmup period I had customer run product in. Verified all operation and unit is working good at this time.


Mark B.

Mark B. Job Checkin

Arrived at location on 1/28/22 - Reported on Wednesday kept filling and dishes have been spotty. Found pin hole in exit side tubing from rinse aid pump to manifold. Cut tubing back and reconnected. Chemical pumped good. Could not find any issue with filling. Could have been a stuck float or debri in valve that passed through. Floats are clean at time of service. Had gotten a message from chad about drain plunger being pushed down too far. Could not duplicate. O ring in tact and seems to be holding. Could of had debri on oring as well. Told staff to keep an eye on it and let us know if issue occurs again.


Mark B.

Mark B. Job Checkin

Arrived at location on 11/15/21 - Installed new fan blade. Applied some epoxy to the press joint on both sides to see if this helps with the longevity of the actual fan blade. I couldn’t find any other options to swap out with when I went to united as all the other motors were a lot larger in diameter with that shaft size. Will see how this works and if it does we will need to do this when we install them in the future.


Mark B.

Mark B. Job Checkin

Arrived at location on 8/5/21 - Evaporator was iced up and fans not running. Located UNMARKED WALK INN FREEZER condenser on the roof and put unit into defrost, Checked heaters and time clock. Clock was moving freely and seemed to be operating properly. Unit pumped down properly and contactor is ok. Removed remaining ice build up and started unit, fans would not come on so I checked power and found bad defrost termination switch. Once replaced fans came on once evap temp was low enough. System is operating properly at this time.


Mark B.

Mark B. Job Checkin

Arrived at location on 6/25/21 with part. Removed old one and installed new vacuum pump and hooked back up and checked operation, ok. Tested ok and got good vacuum.


Libby D.

Libby D. Job Checkin

BUNN COFFEE MACHINE - 04/26/21- Joey- Found unit not brewing and overflowing. head spray head clogged with scale. descaled spray head and unit. brew several batches checked all operation all ok.


Libby D.

Libby D. Job Checkin

WALK IN COOLER - 04/19/21- Tom - Door hinges are worn out and need replaced, Door hinges are reach in hinges, Customer would like a quote on replacing existing hinges and a quote on actual walk in hinges and regardless of what hinge he decides on he would also like a door closer installed on top of door. 04/21/21 - Voided Invoice & Refunded credit card sale (Billed in error)


Libby D.

Libby D. Job Checkin

Traulsen Reach-In Freezer - 04/13/21- Dave-Found unit breaker tripped. Removed wire cover and unhooked compressor then reset breaker. Unit stayed on. Tested compressor relay and found relay faulty. Ran to supply house for replacement relay and capacitor. unit is up and running fine at this time and dropping in temp.


Service C.

Service C. Job Checkin

Came in and installed new gas valve and thermopile on Bakers Pride Oven, tested the unit, unit heats up okay.


Service C.

Service C. Job Checkin

Removed harvest assist assembly and replaced with new part. Turned on Ice machine and found numerous other issues. The water was trying to start but couldn't. Once the pump motor was freed up, The compressor would not start. Tapped on the Ice cube relay, Contactor pulled in and compressor started. The Contactor is pitted and buzzing. Any of these components could fail at any time. Spoke to the facility manager about these issue and he asked to have all the parts quoted, and also quote a new machine. Managers information is attached in file room. Any quotes should be sent to him.