No heat - Upon arrival - unit going through the sequence of operation but gas valve not allowing gas to flow. Verified ventor motor 1.84w.c Pressure switch -1.13 Circuit board is sending 27.63 v to the gas valve. Gas valve no opening up. Replaced gas valve, set gas pressures, tested for leaks. No leaks. Tested system Fully operational See photos