2016 Lennox Single Stage Furnace – Maintenance Visit Work Performed: - Completed full furnace maintenance; furnace operating normally for its age. - Blower wheel/cage is very dirty; recommend full blower wheel cleaning. - Mildew observed on floor due to vinyl condensate tubing from furnace and water heater. Recommend replacing floor drain and converting vinyl tubing to PVC for cleaner drainage and to eliminate mildew. - Ecobee thermostat and furnace controls operating normally. Water Heater: - Client requested water heater maintenance - Minimal maintenance required for this type of unit. -water heater may be a rental Key Maintenance Checks Completed: - Combustion and temperature rise tested within normal range. - Ignition system and flame sensor operation normal. - Pressure switch and safety devices operating properly. - Drain/condensate system inspected; tubing layout contributing to mildew. - Blower compartment inspected; blower wheel heavily dust-coated. Maintenance checklis