Site Visit – Gas Service Assessment & Wall Furnace Inspection (Vacant Property) Attended a service call to assess the condition of the gas system and wall furnace in a vacant property. Gas supply was off and red-tagged by enbridge, with the tag dated from 2023 citing lack of appliance maintenance. Temporarily restored gas to conduct diagnostic testing. Wall Furnace Findings: Wall furnace appears to have been installed by Enercare in 2016 and has a manufacture date of 2016, indicating it is relatively modern and mechanically sound. On startup, pilot and burner ignition produced visible smoke, likely due to dust accumulation on the heat exchanger and internal components. The unit needs to be disassembled and deep cleaned to ensure safe and proper operation. Water Heater & Venting Issues: Water heater is enclosed behind a finished wall, with no access to inspect the venting or verify chimney connection. Access must be created to allow visual inspection of venting and connection integri