Furnace repair - circ blower not moving air. Upon arrival tested furnace blower - not moving. Tested capacitor - blown Tested motor windings to ground - good Tested motor windings - good. Replaced capacitor and tested motor 5.43 amps System is running. Tested A/c - operational Discussed replacing unit and having a plan for the next break down in the system.