Performed Platinum Comfort Club Membership Tune-Up on Cooling System heat pump pressures were 78/320 did clean coils did find a failed single run capacitor on fan side did replace compressor amp draw was approximately 6.98 amps fan .76 did not find any other issues with condensor Performed Platinum Comfort Club Membership Tune-Up on Heating System maintenance on unico tested capacitor blower amps were 5.56 heat strips pulled below 19 amps on both banks temp rise with heatpump was 32 degrees @55 ambient did not find any issues