Service Type: Demand Service – No Cooling Unit sub SN:*** 36GB1F. Living room Issue Reported: Upon arrival, the client stated that the system stopped cooling the previous night. Thermostat was set to 77°F, with an indoor temperature reading of 89°F. Diagnostics & Findings: • Inspected thermostat: Confirmed it was calling for cooling. • Checked air handler: Found it running. • Inspected float (water safety) switch: Found reservoir full of water, causing the system to shut off cooling. • Investigated outdoor condensate discharge: Found line buried underground, restricting proper drainage. Action Taken: • Informed client of the issue and received approval to flush the condensate drain line. • Flushed the line using high-pressure CO₂. • Verified proper drainage and emptied the float switch reservoir. • Confirmed no residual water remained in the system. • Partially unburied the outdoor discharge line for proper drainage. Initially planned to install a 90° elbow to redirect wate