Three 2015 Performed a semi annual cooling service on three split systems. Replaced filters throughout the house and Casita. Cleared condensation lines at furnace and discharge point cycled equipment followed, cooling sequence of operation checked refrigerant/temperature split checked capacitor, hard start, fan motor, compressor, amps and voltage. Secured a clean electrical connections at condenser and fuse box. Thermostat checked out. Rinsed condenser coils. Rinsed, washable filter filters and condenser coil for garage ductless unit. Unit SN ***** 28244 Casita unit While performing maintenance found capacitor completely out of range. The only reason system is starting because it has a hard start that turns compressor on also found condenser fan motor has oil markings around housing indicating condenser is on his way out. Attached is an estimate for recommended repairs Repairs can be performed from outside and tested from outside