Homeowner stated bedroom unit #A91F 2021 Gold American standard wasn’t cooling properly. Found oil markings on top, indicating leak inside compressor area. Confirmed we replaced this compressor July 2024. Found and confirmed leak at discharge line where tubing cutters were used. Covered under parts and labor. System was almost flat. Removed charge, brazed leak point. Pressure tested after and used bubble reactant to confirm. Pulled deep vacuum. Performed decay test, stayed under 500 microns. Added back factory charge 12lbs 10oz. Tested system after and charge and temperature split are good. System is cooling properly now.