Performed annual heating maintenance on a 2016 Carrier 2ton heat pump. Upflow fau located in indoor mechanical closet. Replaced 13x21-1/2 filter located in filter cabinet. Informed to client for future cases, filter may need to be ordered or cut to size. Cleared condensation line. Followed sequence of operations and checked voltage, amperage, capacitor, temperature rise, Freon levels, and secured all electrical connections. Cycled system in cooling and verified LSOV is working properly. Found compressor over amping at start up, recommended to client adding a hard start kit to lower amps at start up and prolong life of compressor. Client authorized recommended repair. Installed, tested, and cycled system. Thermostat checked out operational. System is working properly in heating at this time of service.