Existing air conditioner has a leaking evaporator coil. Cost to install new AC.
Cost to replace air conditioning. Cost to install central air conditioning and humidifier.
Customer was having issues with airflow, technician checked, found a few dampers were shut and also found filter was dirty. Open supply ducts, and replace filter unit is operating with no issues.
Responded to low humidity call found proper voltage at solenoid valve valve stuck closed quoted hh8 for repair. Customer chose option a. Replaced part and 10 wp. Cycled unit on. Unit properly operating at this time. Went over relative humidity parameters and how to turn off and on unit customer chose to sign up for maintenance. Has already had furnace check done this year would like to start with ac in spring. Got on schedule for April 7th 9-12.
Performed yearly maintenance and safety checks on 22 Bryant furnace. 11.13%o2. 31 ppm co in flu. 0 ppm co in supply. 44 degree deltat. Replaced customer supplied 413 filter. Furnace properly cycled into second stage. Running with 6.81%o2. 32 ppm co in flu. 0 ppm co in supply. 55 degree deltat. Cleaned flame sensor. Blew out water trap. 55 ohm igntion. 55 degree also performed yearly maintenance on York air handler. Founs 10 kw heat kit pulling 20A each. 20/20/40. Customer still hearing dripping. Advised shouldn’t have noise in winter months. Blew out drain poured vinegar customer supplied. Advised more vinegar would be beneficial. May need to address come spring.
Performed yearly maintenance and safety checks on 2020 bryant furnace. Cleaned flame sensor and water trap. Primed trap. 49 ohm igntion. Condensation pump operating properly.. Customer does not want humidifier coverage today Furnace running with 12.52%o2. 26 ppm co in flu. 0 ppm co in supply. 55degree delta t. Furnace properly cycled into second stage. Running with 9.16%o2. 16 ppm co in flu. 0ppm co in supply. 65 degree deltat. No issues at this time.
Performed yearly maintenance and safety checks on 11 Lennox furnace. Cleaned flame sensor and pressure port. 10.6 %o2. 14 ppm co in flu. 0 ppm co in supply. 51 degree deltat. 201 filter.
Performed yearly maintenance and safety checks on 2004-2008 Goodman furnace. Cleaned flame sensor. 47 ohm igntion. Found inducer reading high amps. 2.52a. Part has high squeal while running. 45.3 degree deltat. Quoted hm8 for repair. Customer will wait for now. Replaced 16251 filter. Also found no dirt leg on water heater or furnace. Advised with 93 water heater, if changes were made at this point that he likely would need to replace heater. Customer is aware and counting days to replacement. Advised we replace tanked/tankless water heaters. Customer will keep in mind. 56 degree deltat. 35 ppm co in flu. 0 ppm co in supply. Also performed yearly maintenance on 01 airtemp furnace. Replaced 20251 filter. Cleaned flame sensor. 52 ohm ignition. 7.6%o2. 33 ppm co in flu. 0 ppm co in supply 55 degree deltat.
Made call for cooling found compressor failed to start voltage absorption within manufacture specifications. Start and run winding reading 3.4 megaohm. Common winding reading 3 ohm. Failed compressor. Left quote for new ac system. Customer will get more bids and contact if wanting to move forward.
Perofmred yearly maintenance and safety checks on Bryant ac system. Found 35/5 voltage absorption system reading 35/5. Cleaned condenser advised ive has grown into unit. May want to cut back. Customer is planning all Removing all ive in area. 23 degree deltat. No issues. Also perofmred yearly maintenance and safety checks on furnace. Cleared drain with co2 gun.flushed trap. Cycled furnace. Unit running with 9.67%o2. 15 ppm co in flu. 0 ppm co in supply. 111 degree stack temp. Cleaned sensor. 51 degree dletat. Replaced 201 filter. Leak at silinoid valve. Cannot replace part would need to replace humidifier. Hh9a customer stated she cannot do repairs at this time. No issues upon departure
Responded to water leaking on floor. Customer explained water overflowing from t off evap coil. Poured 28 floz water into tee. Found water building up.. another clean out in front of furnace shows no water build up. Blockage between two tees. Flushed drain poured 6/7-28 floz water bottles into drain. Water properly getting disposed. Quoted ho1 for repair due to gold option chosen at last visit. Found male adapter from drain pan broken inside pan. Caulk was used to seal. Advised customer could break pan if trying to extract.. advised he could attempt caulking. Ballparked hf8a for replacement pan. Customer is not interested.