Completed spring maintenance on Rheem package unit. Checked refrigerant levels (subcooling at 12°F), cleaned evaporator coil, and verified proper drainage. Amp draw within specification at 19.2A. Discovered minor duct leakage at plenum connection. Sealed with mastic and verified static pressure improvement from 0.65 to 0.48 inches WC.