ANNUAL FIRE EXTINGUSIHER INSPECTION (6) SEMI-ANNUAL KITCHEN SUPPRESSION INSPECTION Inoperable Deficiency: Detection line failed No detection over 1 fryer Nozzles for fryers need moved to right and adjusted or move fryers to left No nozzle coverage for pizza oven ( replace 3N nozzles with 230 for pizza oven coverage) Replace detection line with ( all detection brackets are welded except for 5 ducts) Repipe nozzles over fryers for proper aim or move to appliances to right Detection bracket needed over 1 fryer Nozzle coverage for pizza oven Ansul detection bracket 50' cable 4 sticks 3/8 pipe 2 sticks conduit 4 1N nozzles 4 3/8 Tees 6 3/8 elbows 2 230 nozzles for cylinder on pizza oven and 2 fryers 3/8 hood seal