Kitchen Suppression Inspection Deficiency: Duct and plenum needs cleaned Obsolete Pulleys on detection line need replaced Cylinder is due for hydro test and hose replacement Regulator test is due All electric appliances do not shutdown when tripped No alarm or alarm bell Clean duct and plenum 4 pulleys Hydro test cylinder and 1 Ansul hose Test regulator Electrician needed 1 micro switch for electric shutdown Needs alarm or alarm bell( micro switch in box)