22645 83rd Ave, S Building D
Kent , WA 98032
206-772-7502

Job Locations
for bellevue, wa


Map of Bellevue WA
Ryan H.

Ryan H.


Job Checkin

Deficiency Repairs Sprinkler Repair 5 year inspection is due. Internal pipe exam of (1) wet & (5) dry sprinkler systems. Backflush of Fire Department connection - Check valve is located at riser and difficult to access. Replacement of (17) water & (6) air gauges. Wet SPK-1 Garage P-2: Painted sprinkler heads: (3) in Room 585 living area. (1) in Room 566 living area. ***Numerous rooms have taped sprinkler heads from the fourth and fifth floor remodeling. This can be addressed by onsite maintenance. (5) Dry sprinkler systems are due for 3 year full trip. **Return trip will be needed to drain all low point drains. ***To be completed in Spring.