Mark B.

Mark B. Job Checkin

Arrived at location on 3/14/23 - Found drain pan frozen and not draining because drain line heater wasn’t working, I thawed ice with a torch and water, I replaced drain line heater from truck stock, I reused drain line insulation and unit is now working properly.


Mark B.

Mark B. Job Checkin

Arrived at location on 9/27/22 - Spoke to manager on duty. I found out the thermostat was broken and not opening and allowing gas to go through. Will order. Returned to location on 9/28/22 - Replaced thermostat tested. Sys ops ok.


Mark B.

Mark B. Job Checkin

Arrived at location on 6/2/22 - Manager said walk in was leaking water. Drain was clogged. Blew out drain and water came out. Drain is now cleared.


Mark B.

Mark B. Job Checkin

Arrived at location on 3/16/22 - Reset hi limit. Checked gas pressure. Good at 4.1”wc. Checked temperature cycle. Unit not cycling correctly. Will need new thermostat. Replaced thermostat and tested. Sys ops ok.


Mark B.

Mark B. Job Checkin

Arrived at location on 8/9/21 - Exhaust will not turn on. Got access to the roof and found out the power was off. Turned unit on and noticed that there weren't any belts on the pulley. Will return with belt to fix issue. Returned to location on 8/10/21 - Verified parts were correct and added both belts to the pulley. I made sure the bearings were properly Lubed and there were a proper tension for the belts. I stored the other belt in side the unit. Unit is now working at this time.


Mark B.

Mark B. Job Checkin

Arrived at location on 7/21/21 - Replaced thermostat, timer and thermometer. Unit is still spitting water out the back at times but not blowing door open. Water level could be part of it. Left a message for factory waiting on return call. Returned to location on 8/4/21 - Replaced pressure switch. Unit heated then heat started dropping and did not kick back on. If I would open the door it would kick the heat on. Found a few clogs in drain/air manifold. Ran unit again and it heated and cycled, ok.


Mark B.

Mark B. Job Checkin

Arrived at location on 7/13/21 - Installed customer combi onto table.


Mark B.

Mark B. Job Checkin

Arrived at location on 6/19/21 - to check on fryer, could not get lit so replaced thermopile lit and heated. Tripped hi limit early at 350. Will order hi limit and wire and return. Cannot find breakdown. Will need parts to id. Returned to location on 7/9/21 - Replaced hi limit and hi limit wire. Tested, heated and cycled ok. Sys ops ok. Capillary bracket is no longer connected to burner tube. If thermostat or hi limit issues occur again may be best to replace unit.


Service C.

Service C. Job Checkin

Reported BEV Reach-In Cooler unit leaking water out door and not going into delime mode. cleaned probes and unit fired up and is cooking properly. tried to put in delime mode but when you get it on power and delime and let go, service lights up and unit goes to just power. will not go into delime mode. spoke to Steven at factory, said it has to be the board. I'm going to order a gasket and manually delime unit. when we return will also call and try to talk to someone else at factory. 3/26/21 I arrived onsite and spoke to MOD. I pulled out bottom element to manually remove some of the scale buildup from the tank. I put the new gasket for the element in place and filled up the tank. I manually added descaler to the unit and ran it through. After I drained and fill unit 2 times, called tech support and spoke to James. Found that the board is not working properly in the clean mode. Customer doesn't want to replace because unit still works for cooking.


Service C.

Service C. Job Checkin

1-11-21 Checked out Bunn Coffee Machine unit and found the element is leaking so tried to see if the nut was loose and it was so tightened it. drained the tank and unplugged it and will order a new element for unit. 1-13-21 I arrived onsite and spoke to MOD. While removing inner heater I noticed how corroded the outer element was. Will need to replaced to release inner element. 1-20-21 I arrived onsite and spoke to MOD. I verified that part was correct and began to remove old elements. After installing, I checked for leaks. The amp reading was 15.3. Unit is working at this time and is in fair condition.


Service C.

Service C. Job Checkin

Upon arrival, both Reach-In Freezer units overheated and cycling on compressor overload. Customer stated kitchen A/C was not working and was in the midst of repair. Also stated filters were dirty and needed cleaned/replaced. Ambient temperature in kitchen 108°F at this time. Cooled off compressor manually and unit ran for 5-7 minutes and shut off again on overload. Compressor ampdraw good and windings checking out good, units not low on refrigerant. Advised customer of same issue with both units and advised they should leave units off to allow compressors to cool entirely until kitchen at appropriate conditioned temperature. Units off at this time, product removed, and customer will power back on once compressors have time to cool and kitchen A/C working properly.


Service C.

Service C. Job Checkin

Convection Oven Unit working upon arrival. Reported sometimes will stop heating and will have to turn off and back on to get unit working. Found flame sense 3.5ua. found igniter wire burnt up and brittle. Installed spare wire for time being will order 1=55648= ignition wire. cooling fans working but heavily covered in dust. cleaned. ignition module may have also been damaged by heat as a result. spoke to Athen, will order igniter wire. if it happens in the meantime he will call and have us order the module. 2-26-20 Actual problem is with bottom convection oven. Replaced previously ordered ignition cable. Reinforced with high temp sheathing and high temp tape. Tested okay.


Service C.

Service C. Job Checkin

Disposer Motor receiving 211 volts 3 phase. pulling only 4 amps but motor is making loud noise. Nothing jammed in unit. will quote new unit. send quote to azs441@psu.edu and gqs1@psu.edu


Service C.

Service C. Job Checkin

Replaced 2 door gaskets and ensured that the Prep Table unit is operating properly.


Service C.

Service C. Job Checkin

Took latch assembly from other Sterilizer unit and put it on this one. tested, system ops okay.