Homeowner stated guest bedrooms (2) were warmer than rest of home. Checked out system temperatures and getting proper supply temperatures and split (21). Checked out the layout, guest bedroom by courtyard is on master zone, and guest bedroom in center of home is on living room zone. dampers are opening fully and when called for. Informed that zones and system are working properly. Recommended either running each respective zone at lower temp so guest rooms reach preferred temperature or add (2) room temperature sensors so system will run until each bedroom is at temp set at thermostat. Recommended Hyde’s comfort club maintenance plan and left brochure. Attached is estimates for room sensors (without 15% maintenance plan discount) and our comfort club silver membership (most popular)