Performed a cooling maintenance on a carrie condenser, condenser located on left side of home, filter located hallway ceiling and master bedroom ceiling, fau located in attic, changed filter, flushed condensation line, on condenser check for amperage and voltage, check for compressor, check for capacitor as in condenser s#0312 capacitor was out of range in compressor side 45/7.5 was reading 43/7.5 advice HO which okay to replace capacitor, check for freon level, everything within range , clear out dust accumulated inside electrical component area and rinsed condenser coil. System is working within specification in cooling at the time of maintenance. (Renewed HFCP)