Service Type: Demand Service Unit Serial Number: *****6P31F (Back Bedrooms Unit) Technician Summary: Upon arrival, the client reported that the bedroom unit was not functioning. I inspected the thermostat, which was set to 78°F, while the indoor temperature was reading 83°F—indicating the thermostat was calling for cooling but the system was not responding. I proceeded to inspect the equipment. First, I verified that power was present at both the condenser and furnace. I also confirmed the presence of 24V at the circuit board and the communicating relay panel. (Note: Thermostat is a wireless model.) I then bypassed the thermostat to rule it out as the issue; however, the system still did not initiate any functions. All wiring and connections were verified to be intact. Based on these findings, I determined that the circuit board has failed. Next Steps: • Will contact American Standard on Monday to obtain replacement parts. • Will follow up with the client to provide an ETA for