Performed heating maintenance on 2018 Goodman split heat pump. Changed 14x30 filter with filter register, no ladder. Cleared condensation drain. Removed debris/pet hair from return area. Inspected evaporator coil and blower wheel for cleanliness, found them dirty. Honeywell 6000 thermostats working properly. Checked 10uf blower motor capacitor, within range. Checked amps, volts, and temp rise (30°). System is fully operational and heating to manufacturer specifications. I found a couple issues that I recommend addressing. I found the evaporator coil is dirty and building up debris, this can lead to ice forming on the coil and turning into a solid ice block during summer. And can shut off on high pressure during heat mode. Deep cleaning of coil is recommended, quote attached with this report. Second recommendation is to have a Jones valve installed on the drain line. This system has had issues with condensation overflow in the past. System is protected with a water safety switch. Howeve