Upon arrival kitchen system has same 6x flash code from diagnostic module indicating open start circuit. Inspected wiring and harness and found windings again and all are good and complete circuit. Based off manual, it shuts off thermostat ability to cool when flash appears when the module doesn’t sense amperage. Did find capacitor weaker than before and out of range at 32uf out of 40uf. Replaced and tested and system is running properly. Amps never cut out on any windings, specifically start winding. Filters good, high temp split but cooling good, could be just location of thermometer. . If issue persists my opinion is it’s the module somehow not sensing the current and popping up alert flash.