Upon arrival found all loads operational. Thermostat set for cool, indoor 84, setpoint 70. Found suction line with frost. Found 5” media filter completely restricted with drywall debris. Removed and replaced with new filter. Disconnected power to condenser until all frost and ice was melted. Inspected coil and it was completely thawed out. Powered condenser back on. Balanced charge about less than a pound of r410a. Vsat around 46 and line temps around 63, as long as filters are replaced regularly issue should not return. Locked up home and put key back in lock box,