Upon arrival, checked capacitor and capacitor on compressor side was weak. Installed no 45/5 MFD CAPACITOR. RESET BREAKER AND CHECKED AMPS ON COMPRESSOR AND CONDENSER FAN MOTOR. COMPRESSOR IS RATED FOR 14.1 A AND IS PULLING 6.8, CONDENSER FAN MOTOR IS RATED FOUR POINTS 64 A AND IS PULLING 4.4 A. ALSO CHECKED TOTAL AMPS ON AIR HANDLER TOTAL AMPS IS RATED FOR 7.5 AND UNIT IS PULLING 4.5. No issue with system could be found at this time.client has JB extended warranty