Cool check completed on an up-flow furnace system. Float switch is working properly. Drain line has been cleared. Blower motor capacitor is below manufacture specs. Outdoor condenser amp draws are within spec. The coil is clean and refrigerant levels are normal. Outdoor capacitor is also within spec; however, the contactor is chard and pitted. No other major issues found.