184.05 alert preceding hard lock out. Tested system and sensors at low and high speed demand minimum-100%, system charge and amps/volts to specs. Suction line temperature sensor off about. 5°. Adjusted location and tightness til it was about 1-2° off. No alerts or derating during call. Will get with manufacturer and management about possible issue. 3 drive tests all passed.